S7 Plus

S7 Plus is the symbolic half of S7: a variable is addressed by its name in the PLC program rather than by a byte offset. It works with S7-1200 and S7-1500 CPUs.

Its most practical consequence: you do not have to turn off optimized block access on your DBs. The TIA Portal step that causes most of the trouble with classic S7 does not exist here.

The S7 Plus data model Connection carries TLS and the timeout; Device the polling interval; Frame the batch read together; Variable the symbol access sequence and type. Connection TLS trust and the timeout — no rack or slot Device the polling interval Frame no address — the batch read together Variable the symbol access sequence and data type
ParameterDefaultDescription
ProtocolS7 Plus—
IP Address—The CPU’s address
Port102—
Timeout (ms)—At least 100
Certificate Fingerprint—The pinned fingerprint of the CPU’s certificate
Trust Any CertificateoffAccept any certificate

There is no rack or slot. S7comm-plus connects to a fixed TSAP and the CPU answers whatever its rack and slot are, so those fields would ask for something that is never sent.

S7comm-plus speaks inside a TLS tunnel carried in COTP frames, and the CPU’s certificate is self-signed — there is no authority for a public trust store to check it against. The question “is this the right CPU” has only two honest answers: you pin the certificate’s fingerprint, or you deliberately say any certificate will do.

ParameterDescription
Scan TimeThe polling interval (at least 100 ms)
Scan TypePERIODIC or FIXED_DELAY

A frame has one field, and it is not an address:

ParameterDefaultDescription
Use Subscription ModeoffTake values from the CPU’s notifications

With it off the frame is polled; with it on the CPU reports changes itself. The default is off because a subscription costs a frame per cycle even while nothing changes.

ParameterDescription
Access SequenceThe symbol’s access sequence — filled in by the browse
TypeThe data type — filled in by the browse
Symbol CRCThe symbol’s checksum, kept for the drift check

A member of a nested struct and an element of an array can be picked too: they are addressed by a path of several identifiers, and the whole path travels in the access sequence.

BOOL, BYTE, WORD, INT, DWORD, DINT, REAL, LREAL, LWORD, USINT, UINT, UDINT, ULINT, SINT, LINT

You do not declare the data type: in classic S7 the operator must, because the CPU does not hold the symbol table; here the browse fills it in from what the CPU reported.

The CPU’s symbol catalogue is browsed and variables are picked from the list. A symbol the catalogue could not address at all — a type object the CPU did not send, a type that contains itself, a list cut at its size limit — appears not as a pickable variable but as a notice saying why.

What inSCADA does about it: the catalogue gives a CRC for each symbol, and the browse writes it into the variable’s configuration. When the program is recompiled the CRC changes even if the name does not, so comparing the two CRCs answers whether that address is something else now.

The comparison is done on the inSCADA side. The protocol’s request has a checksum field, and had the CPU validated it the check would have been server-side — the strongest form; but when measured, this firmware rejected a correct checksum and a wrong one with the same return value, meaning it does not accept the field at all.

In practice: re-browse the symbols after every download to the PLC program. If a symbol has drifted, the comparison says so.