BACnet Client
In Client mode inSCADA connects to BACnet/IP devices to read and write their object values.
Step 1: creating the connection
Section titled “Step 1: creating the connection”The connection’s ip and port are the server’s own local socket — not the target device’s. The target address is given at device level.
| Parameter | Default | Range |
|---|---|---|
| Protocol | BACnet | — |
| APDU Timeout (ms) | 3000 | 100 – 60000 |
| Retries | 3 | 0 – 10 |
Step 2: creating the device
Section titled “Step 2: creating the device”| Parameter | Default | Description |
|---|---|---|
| Device Instance | — | The device’s instance number (0 – 4194302) |
| IP | — | The device’s address |
| Port | 47808 | The standard BACnet/IP port |
| Network | — | On a routed device, the far network’s number (1 – 65534) |
| MAC Address | — | The device’s MAC on that network |
| Scan Time | — | The polling interval |
| Scan Type | — | PERIODIC or FIXED_DELAY |
Step 3: creating frames
Section titled “Step 3: creating frames”A frame groups the objects that are read together.
| Parameter | Default | Description |
|---|---|---|
| Use Subscription Mode | off | Take values from COV notifications instead of polling |
Step 4: creating variables
Section titled “Step 4: creating variables”| Parameter | Default | Description |
|---|---|---|
| Object Type | — | The object type (0 – 1023) |
| Object Instance | — | The object’s instance number (0 – 4194303) |
| Property Id | 85 | The property to read; 85 is Present_Value |
| Array Index | — | The element index on an array property |
| Write Priority | 16 | The write priority (1 – 16) |
| Type | — | FLOAT, INTEGER, BOOLEAN or STRING |
Typical variables
Section titled “Typical variables”| Variable | Object type | Property | Description |
|---|---|---|---|
| Room temperature | 0 (Analog Input) | 85 | The measured temperature |
| Setpoint | 2 (Analog Value) | 85 | A writable setting |
| Fan status | 3 (Binary Input) | 85 | Running / stopped |
| Fan command | 4 (Binary Output) | 85 | On / off |
| Operating mode | 19 (Multi-state Value) | 85 | The mode number |
Step 5: starting the connection
Section titled “Step 5: starting the connection”Start the connection from the Runtime Control Panel. Its status will show “Connected”.