IEC 61850 Server

In Server mode inSCADA lets external IEC 61850 clients — a higher-level SCADA, a control centre, another IED — connect and read data from it over MMS.

  • Presenting data to a higher-level SCADA over IEC 61850 MMS
  • IEC 61850 communication between separate inSCADA installations
  • As a gateway in substation automation — presenting data gathered over other protocols in IEC 61850 form
ParameterExampleDescription
ProtocolIEC 61850 ServerThe protocol
Port102The listening port (for incoming connections)
SCL File Content(the file)The SCL file describing the data model to present

In server mode the SCL file describes the data model inSCADA will present to the outside world. It decides:

  • which logical devices are presented
  • the logical nodes under each one
  • the data objects and data attributes under each node

These are defined exactly as in client mode. The values of the variables you define are presented to the connected clients over MMS.

IEC 61850 Server gateway Data collected from field devices over several protocols is presented upwards through inSCADA as IEC 61850 Server (MMS, port 102). Field devices — relays, RTUs, meters Modbus, IEC 104, DNP3, … inSCADA data collection IEC 61850 Server (MMS, port 102) Higher-level SCADA / control centre IEC 61850 Client

Here inSCADA collects data from field devices over several different protocols and presents it upwards as an IEC 61850 MMS server. It is used above all in substation automation, to present data gathered from different manufacturers’ IEDs in one standard form.