IEC 104 Server (Slave)

In Server (Slave) mode inSCADA lets external master stations connect and read data from it. The mode is typically used to:

  • present data over IEC 104 to a higher-level SCADA or control centre
  • share data between distribution centres
  • carry IEC 104 communication between separate inSCADA installations
ParameterExampleDescription
ProtocolIEC 60870-5-104 ServerThe protocol
Port2404The listening port (for incoming connections)
Buffering Period1000 msThe data buffering interval

The remaining connection parameters (t1, t2, t3, k, w and the field lengths) have the same shape as on the client and must match the master that connects.

These are defined exactly as in client mode. The values of the variables you define are presented to the connected master as IEC 104 ASDUs.

In server mode inSCADA sends a spontaneous event to the connected master by itself whenever a variable’s value changes. The Buffering Period parameter decides how often those events go out.

IEC 104 Server gateway Data collected from field devices over several protocols is presented upwards through inSCADA as IEC 104 Server. Field devices Modbus, DNP3, OPC UA, … inSCADA data collection IEC 104 Server Higher-level SCADA / control centre IEC 104 Master

Here inSCADA collects data from field devices over several different protocols and presents it upwards as an IEC 104 server — acting as a protocol gateway.