In Master mode inSCADA connects to field devices (RTUs, IEDs, relays and the like) to read data and send control commands.
| Parameter | Example | Description |
|---|
| Protocol | DNP3 | The protocol |
| IP Address | 192.168.1.50 | The target outstation’s IP address |
| Port | 20000 | The target port (default: 20000) |
| Adapter | (empty) | The network adapter (for a host with several NICs) |
| Pool Size | 1 | The connection pool size |
| Min Retry Delay | 1000 ms | The shortest wait before reconnecting |
| Max Retry Delay | 60000 ms | The longest wait before reconnecting |
| Parameter | Example | Description |
|---|
| Local Address | 1 | The master’s DNP3 address |
| Remote Address | 10 | The outstation’s DNP3 address |
| Response Timeout | 5000 ms | How long a response is waited for |
| Integrity Scan Time | 60000 ms | The integrity scan interval (all static data) |
| Event Scan Time | 5000 ms | The event scan interval (class 1/2/3) |
| Scan Type | PERIODIC | PERIODIC or FIXED_DELAY |
| Unsolicited Events | true | Accept unsolicited responses |
| Disable Unsolicited on Startup | false | Turn unsolicited off at startup |
| Startup Integrity | true | Run an integrity scan at startup |
| Integrity on Event Overflow IIN | true | Run an integrity scan when the event buffer overflows |
Define one frame per data group:
| Parameter | Example | Description |
|---|
| Type | Analog Input | The data type |
| Start Address | 0 | The first point index |
| Quantity | 10 | How many points |
| Event Buffer Size | 100 | The event buffer size |
| Point Class | Class 1 | The event class |
| Static Variation | Group30Var5 | 32-bit float (with flag) |
| Event Variation | Group32Var7 | 32-bit float (timestamped) |
| Deadband | 0.5 | The analogue event threshold |
| Frame name | Type | Start | Quantity | Used for |
|---|
| Analog Inputs | Analog Input | 0 | 20 | Temperature, pressure and current measurements |
| Binary Inputs | Binary Input | 0 | 32 | Digital state information |
| Counters | Counter | 0 | 8 | Energy meters |
| Binary Outputs | Binary Output | 0 | 16 | Control outputs |
| Parameter | Example | Description |
|---|
| Start Address | 0 | The point index |
| Point Class | Class 1 | The event class (may be inherited from the frame) |
| Static Variation | Group30Var5 | The static data format |
| Event Variation | Group32Var7 | The event data format |
| Deadband | 0.5 | The analogue event threshold |
Start the connection from the Runtime Control Panel. Its status will show “Connected”.
The master can send an outstation:
- Select-Before-Operate (SBO): select first, then operate — the safe form of control
- Direct Operate: operate immediately
- Freeze Accumulator: freeze a counter
- Time synchronisation: set the outstation’s clock