KNX
KNX is the field bus of building automation: lighting, blinds, heating, ventilation. inSCADA supports KNXnet/IP natively — no separate gateway application is involved.
Addressing
Section titled “Addressing”A KNX group address is not a byte offset, so start address is not used. The hierarchy sits like this:
| Level | What it carries |
|---|---|
| Connection | An IP interface, or the routing backbone |
| Device | A logical container — KNX has no device address |
| Frame | A main/middle group from ETS |
| Variable | A group address and its DPT |
Connection modes
Section titled “Connection modes”| Mode | What it does |
|---|---|
TUNNEL_UDP | A UDP tunnel to a KNXnet/IP interface (the default) |
TUNNEL_TCP | The same over TCP |
ROUTING | Joins the routing backbone by multicast |
In routing mode, with no address given, the standard multicast group 224.0.23.12 is used; the default port is 3671.
Connection fields
Section titled “Connection fields”| Field | Default | Description |
|---|---|---|
| Individual Address | — | inSCADA’s own address on the bus |
| Requested Address | — | The address to ask the interface for on a tunnel |
| Local Address | — | Which adapter to go out of, on a host with several |
| NAT Mode | off | For connections behind NAT |
| Min Send Interval (ms) | 50 | The shortest gap between two telegrams |
| Read Timeout (ms) | 2000 | How long a read response is waited for |
| Initial Read Interval (ms) | 250 | The gap between the initial reads at startup |
| Router Check Interval (s) | 30 | The poll interval in routing mode |
| Heartbeat Interval / Timeout / Retries | 60 s / 10 s / 3 | The tunnel’s liveness check |
Variable fields
Section titled “Variable fields”| Field | Description |
|---|---|
| Group Address | Where a write goes |
| Status Group Address | The actuator’s feedback address — this is what is read |
| Listen Group Addresses | Further addresses carrying the same value |
| DPT | The data point type |
| DPT Field | Which field of a composite DPT |
| Type | FLOAT, INTEGER, BOOLEAN or STRING |
| Status Only | Read-only |
| Expire (s) | How long before the value is considered stale |
A group address is accepted in all three of KNX’s spellings: 1/2/3, 1/515 and 2563 are the same address.
The address and the DPT are checked at the save: a mistyped address would be a variable no telegram ever reaches, and a DPT the library does not know one that is never decoded. Both are refused then rather than found later by silence.
Discovering interfaces
Section titled “Discovering interfaces”inSCADA can find the KNXnet/IP interfaces and routers on the network, so a connection’s mode, address and port are picked from a list rather than typed. The search does not leave the local network.
Importing from an ETS project
Section titled “Importing from an ETS project”Uploading an ETS project file reads its group addresses and DPTs. There are three steps:
| Step | What it does |
|---|---|
| Read | Extracts the project’s group structure and addresses |
| Audit | Lists the problems before anything is imported |
| Plan | Shows which frames and variables would be created |
Related